2/0 AWG Voltage Drop — Max Run Length by Load
Voltage drop for 2/0 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 928 ft one-way. Full table by load, voltage and distance.
Quick answer
2/0 AWG copper reaches 3% voltage drop at about 928 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 0.39 V (0.32%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 133,077 circular mils.
3% limit @ 20 A, 120 V
928ft
3% limit @ 20 A, 240 V
1856ft
Drop @ 100 ft, 20 A
0.39V
Ω / 1000 ft (Cu)
0.0779
Maximum one-way run length at 3% drop
Copper 2/0 AWG. Aluminium distances are roughly 62% of these figures.
| Load | 120 V 1Ø | 240 V 1Ø | 208 V 3Ø | 480 V 3Ø |
|---|---|---|---|---|
| 5 A | 3,713 ft | 7,427 ft | 7,433 ft | 17,153 ft |
| 10 A | 1,856 ft | 3,713 ft | 3,716 ft | 8,576 ft |
| 15 A | 1,237 ft | 2,475 ft | 2,477 ft | 5,717 ft |
| 20 A | 928 ft | 1,856 ft | 1,858 ft | 4,288 ft |
| 25 A | 742 ft | 1,485 ft | 1,486 ft | 3,430 ft |
| 30 A | 618 ft | 1,237 ft | 1,238 ft | 2,858 ft |
| 40 A | 464 ft | 928 ft | 929 ft | 2,144 ft |
| 50 A | 371 ft | 742 ft | 743 ft | 1,715 ft |
| 60 A | 309 ft | 618 ft | 619 ft | 1,429 ft |
| 80 A | 232 ft | 464 ft | 464 ft | 1,072 ft |
| 100 A | 185 ft | 371 ft | 371 ft | 857 ft |
Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.
Voltage drop by distance at common loads
| Distance | 10 A | 15 A | 20 A | 30 A |
|---|---|---|---|---|
| 25 ft | 0.04% | 0.06% | 0.08% | 0.12% |
| 50 ft | 0.08% | 0.12% | 0.16% | 0.24% |
| 75 ft | 0.12% | 0.18% | 0.24% | 0.36% |
| 100 ft | 0.16% | 0.24% | 0.32% | 0.48% |
| 150 ft | 0.24% | 0.36% | 0.48% | 0.73% |
| 200 ft | 0.32% | 0.48% | 0.65% | 0.97% |
| 300 ft | 0.48% | 0.73% | 0.97% | 1.45% |
Published standard — source: Voltage drop from the standard VD formula with trade K constants
Frequently asked
- How far can you run 2/0 AWG wire?
- At 20 A on a 120 V single-phase circuit, 2/0 AWG copper stays under 3% voltage drop for about 928 ft one-way. At 240 V the same load reaches roughly 1856 ft, because allowable drop scales with system voltage.
- What is the voltage drop of 2/0 AWG wire per 100 feet?
- About 0.39 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
- Is 3% voltage drop a code requirement?
- It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
- Does aluminium change the 2/0 AWG numbers?
- Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.
More on 2/0 AWG
Related charts & calculators
- Voltage Drop CalculatorPercent drop, end voltage and minimum conductor for any run length.
- Conduit Fill CalculatorFill percentage and maximum conductor count for EMT, RMC, IMC and PVC.
- Breaker Size CalculatorOvercurrent device rating and minimum conductor from load current.
- Wire Ampacity CalculatorDerated ampacity for ambient temperature and bundled conductors.
- Box Fill CalculatorVolume allowances for conductors, clamps, devices and grounds per NEC 314.16.
- Ampacity ChartEstimated allowable ampacity by conductor size, material and insulation rating.