2/0 AWG Voltage Drop — Max Run Length by Load

Voltage drop for 2/0 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 928 ft one-way. Full table by load, voltage and distance.

Quick answer

2/0 AWG copper reaches 3% voltage drop at about 928 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 0.39 V (0.32%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 133,077 circular mils.

3% limit @ 20 A, 120 V

928ft

3% limit @ 20 A, 240 V

1856ft

Drop @ 100 ft, 20 A

0.39V

Ω / 1000 ft (Cu)

0.0779

Maximum one-way run length at 3% drop

Copper 2/0 AWG. Aluminium distances are roughly 62% of these figures.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
5 A3,713 ft7,427 ft7,433 ft17,153 ft
10 A1,856 ft3,713 ft3,716 ft8,576 ft
15 A1,237 ft2,475 ft2,477 ft5,717 ft
20 A928 ft1,856 ft1,858 ft4,288 ft
25 A742 ft1,485 ft1,486 ft3,430 ft
30 A618 ft1,237 ft1,238 ft2,858 ft
40 A464 ft928 ft929 ft2,144 ft
50 A371 ft742 ft743 ft1,715 ft
60 A309 ft618 ft619 ft1,429 ft
80 A232 ft464 ft464 ft1,072 ft
100 A185 ft371 ft371 ft857 ft

Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.

Voltage drop by distance at common loads

Distance10 A15 A20 A30 A
25 ft0.04%0.06%0.08%0.12%
50 ft0.08%0.12%0.16%0.24%
75 ft0.12%0.18%0.24%0.36%
100 ft0.16%0.24%0.32%0.48%
150 ft0.24%0.36%0.48%0.73%
200 ft0.32%0.48%0.65%0.97%
300 ft0.48%0.73%0.97%1.45%
Percent drop, 120 V single phase, copper.
Published standard — source: Voltage drop from the standard VD formula with trade K constants

Frequently asked

How far can you run 2/0 AWG wire?
At 20 A on a 120 V single-phase circuit, 2/0 AWG copper stays under 3% voltage drop for about 928 ft one-way. At 240 V the same load reaches roughly 1856 ft, because allowable drop scales with system voltage.
What is the voltage drop of 2/0 AWG wire per 100 feet?
About 0.39 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
Is 3% voltage drop a code requirement?
It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
Does aluminium change the 2/0 AWG numbers?
Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.