1/0 AWG Breaker Size — Amps & Overcurrent Rating

1/0 AWG copper is estimated at 146 A at 75 °C, which supports a 125 A overcurrent device. Breaker pairing, continuous-load sizing and derating shown.

Quick answer

1/0 AWG copper pairs with a 125 A breaker at 75 °C terminations, from an estimated ampacity of 146 A. Aluminium of the same size is about 114 A. A continuous load on that circuit should not exceed 117 A, since continuous loads are sized at 125%.

Max breaker (Cu, 75 °C)

125A

Copper 60 / 75 / 90 °C

124 / 146 / 165A

Aluminium 75 °C

114A

Max continuous load

117A

Ampacity and breaker pairing

Estimated ampacity by material and insulation temperature rating, with the largest standard device each supports.

Material60 °C75 °C90 °CMax device @ 75 °C
Copper124 A146 A165 A125 A
Aluminium97 A114 A129 A110 A
Formula estimate — source: Ampacity from the site power-law model, not a code table

Derated ampacity and the device that still fits

Ambient temperature and conductor count reduce the usable ampacity before the breaker is chosen.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
3165 A → 125 A151 A → 125 A135 A → 125 A117 A → 110 A
6132 A → 125 A121 A → 110 A108 A → 100 A93 A → 90 A
9115 A → 110 A105 A → 100 A94 A → 90 A82 A → 80 A
1583 A → 80 A75 A → 70 A67 A → 60 A58 A → 50 A
2574 A → 70 A68 A → 60 A61 A → 60 A52 A → 50 A
90 °C insulation, copper, capped in practice by the 75 °C termination rating.

Source & method: Continuous-load example: a 117 A continuous load needs 146 A of design current and a 150 A device. Size your own load.

Neighbouring sizes

Frequently asked

What breaker size for 1/0 AWG wire?
1/0 AWG copper at 75 °C terminations supports up to a 125 A overcurrent device, based on an estimated ampacity of 146 A. Aluminium of the same size supports less: about 114 A.
How many amps can 1/0 AWG handle?
Estimated 124 A at 60 °C, 146 A at 75 °C and 165 A at 90 °C for copper, at 30 °C ambient with no more than three current-carrying conductors.
How does a continuous load change the breaker size?
Continuous loads are sized at 125% of the load current before rounding up to the next standard device rating, so a breaker carries no more than 80% of its rating continuously.
Can the breaker be larger than the wire ampacity?
Only in specific permitted cases such as motor and transformer circuits, where the device protects against short circuit and ground fault while overload protection is provided separately. For ordinary branch circuits, the device must not exceed the conductor ampacity after derating.