1/0 AWG Conduit Fill — Wires per Conduit Size

How many 1/0 AWG THHN conductors fit in EMT, IMC, RMC and PVC conduit, from 1/2 inch through 4 inch, with the 40% fill rule applied.

Quick answer

No 1/0 AWG THHN conductors fit in 1/2 inch EMT and 1 fit in 3/4 inch EMT, at 40% fill for three or more conductors. Each conductor consumes 0.1855 sq in from a nominal insulated outside diameter of 0.486 in. Neutrals and grounds count.

1/0 AWG conductors per conduit trade size

Same-size conductors only, at 53% for one, 31% for two and 40% for three or more.

Conduit1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
EMT1134712192431
IMC1134711172229
RMC1134710162127
PVC Sch 401134710152027
PVC Sch 80112368131824
Published standard — source: Raceway internal areas from product standards (EMT, IMC, RMC, PVC Sch 40, PVC Sch 80); conductor OD from nominal THHN dimensions

Source & method: Counts are the largest whole number where n × conductor area stays inside the raceway area times the applicable fill percentage. Mix conductor sizes in the calculator.

What each raceway type means

  • EMT EMT (electrical metallic tubing)
  • IMC IMC (intermediate metal conduit)
  • RMC RMC (rigid metal conduit)
  • PVC Sch 40 PVC Schedule 40
  • PVC Sch 80 PVC Schedule 80

Frequently asked

How many 1/0 AWG wires fit in 1/2 inch EMT?
None — this size does not fit 1/2 inch EMT; step up a trade size.
How many 1/0 AWG wires fit in 3/4 inch EMT?
1 conductors, using a nominal THHN outside diameter of 0.486 in and the 40% fill rule for three or more conductors.
Do neutrals and grounds count toward fill?
Yes, every conductor in the raceway counts for fill. Grounds are excluded only from the count of current-carrying conductors used for ampacity adjustment.
What is the cross-sectional area of 1/0 AWG THHN?
About 0.1855 square inches, from A = π × (OD / 2)² with a nominal insulated OD of 0.486 in.

More on 1/0 AWG