1/0 AWG Voltage Drop — Max Run Length by Load

Voltage drop for 1/0 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 736 ft one-way. Full table by load, voltage and distance.

Quick answer

1/0 AWG copper reaches 3% voltage drop at about 736 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 0.49 V (0.41%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 105,535 circular mils.

3% limit @ 20 A, 120 V

736ft

3% limit @ 20 A, 240 V

1472ft

Drop @ 100 ft, 20 A

0.49V

Ω / 1000 ft (Cu)

0.0983

Maximum one-way run length at 3% drop

Copper 1/0 AWG. Aluminium distances are roughly 62% of these figures.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
5 A2,945 ft5,890 ft5,894 ft13,603 ft
10 A1,472 ft2,945 ft2,947 ft6,801 ft
15 A981 ft1,963 ft1,964 ft4,534 ft
20 A736 ft1,472 ft1,473 ft3,400 ft
25 A589 ft1,178 ft1,178 ft2,720 ft
30 A490 ft981 ft982 ft2,267 ft
40 A368 ft736 ft736 ft1,700 ft
50 A294 ft589 ft589 ft1,360 ft
60 A245 ft490 ft491 ft1,133 ft
80 A184 ft368 ft368 ft850 ft
100 A147 ft294 ft294 ft680 ft

Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.

Voltage drop by distance at common loads

Distance10 A15 A20 A30 A
25 ft0.05%0.08%0.1%0.15%
50 ft0.1%0.15%0.2%0.31%
75 ft0.15%0.23%0.31%0.46%
100 ft0.2%0.31%0.41%0.61%
150 ft0.31%0.46%0.61%0.92%
200 ft0.41%0.61%0.81%1.22%
300 ft0.61%0.92%1.22%1.83%
Percent drop, 120 V single phase, copper.
Published standard — source: Voltage drop from the standard VD formula with trade K constants

Frequently asked

How far can you run 1/0 AWG wire?
At 20 A on a 120 V single-phase circuit, 1/0 AWG copper stays under 3% voltage drop for about 736 ft one-way. At 240 V the same load reaches roughly 1472 ft, because allowable drop scales with system voltage.
What is the voltage drop of 1/0 AWG wire per 100 feet?
About 0.49 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
Is 3% voltage drop a code requirement?
It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
Does aluminium change the 1/0 AWG numbers?
Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.