750 kcmil Voltage Drop — Max Run Length by Load

Voltage drop for 750 kcmil copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 5232 ft one-way. Full table by load, voltage and distance.

Quick answer

750 kcmil copper reaches 3% voltage drop at about 5232 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 0.07 V (0.06%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 750,000 circular mils.

3% limit @ 20 A, 120 V

5232ft

3% limit @ 20 A, 240 V

10465ft

Drop @ 100 ft, 20 A

0.07V

Ω / 1000 ft (Cu)

0.0138

Maximum one-way run length at 3% drop

Copper 750 kcmil. Aluminium distances are roughly 62% of these figures.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
5 A20,930 ft41,860 ft41,892 ft96,675 ft
10 A10,465 ft20,930 ft20,946 ft48,337 ft
15 A6,976 ft13,953 ft13,964 ft32,225 ft
20 A5,232 ft10,465 ft10,473 ft24,168 ft
25 A4,186 ft8,372 ft8,378 ft19,335 ft
30 A3,488 ft6,976 ft6,982 ft16,112 ft
40 A2,616 ft5,232 ft5,236 ft12,084 ft
50 A2,093 ft4,186 ft4,189 ft9,667 ft
60 A1,744 ft3,488 ft3,491 ft8,056 ft
80 A1,308 ft2,616 ft2,618 ft6,042 ft
100 A1,046 ft2,093 ft2,094 ft4,833 ft

Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.

Voltage drop by distance at common loads

Distance10 A15 A20 A30 A
25 ft0.01%0.01%0.01%0.02%
50 ft0.01%0.02%0.03%0.04%
75 ft0.02%0.03%0.04%0.06%
100 ft0.03%0.04%0.06%0.09%
150 ft0.04%0.06%0.09%0.13%
200 ft0.06%0.09%0.11%0.17%
300 ft0.09%0.13%0.17%0.26%
Percent drop, 120 V single phase, copper.
Published standard — source: Voltage drop from the standard VD formula with trade K constants

Frequently asked

How far can you run 750 kcmil wire?
At 20 A on a 120 V single-phase circuit, 750 kcmil copper stays under 3% voltage drop for about 5232 ft one-way. At 240 V the same load reaches roughly 10465 ft, because allowable drop scales with system voltage.
What is the voltage drop of 750 kcmil wire per 100 feet?
About 0.07 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
Is 3% voltage drop a code requirement?
It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
Does aluminium change the 750 kcmil numbers?
Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.