750 kcmil Conduit Fill by Conduit Size

How many 750 kcmil THHN conductors fit in EMT, IMC, RMC and PVC conduit, 1/2 inch through 4 inch, with the 40% fill rule applied.

Quick answer

No 750 kcmil THHN conductors fit in 1/2 inch EMT and 0 fit in 3/4 inch EMT, at 40% fill for three or more conductors. Each conductor consumes 1.0532 sq in from a nominal insulated outside diameter of 1.158 in. Neutrals and grounds count.

750 kcmil conductors per conduit trade size

Same-size conductors only, at 53% for one, 31% for two and 40% for three or more.

Conduit1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
EMT————111345
IMC————111345
RMC————111234
PVC Sch 40—————11234
PVC Sch 80—————11134
Published standard — source: Raceway internal areas from product standards (EMT, IMC, RMC, PVC Sch 40, PVC Sch 80); conductor OD from nominal THHN dimensions

Source & method: Counts are the largest whole number where n × conductor area stays inside the raceway area times the applicable fill percentage. Mix conductor sizes in the calculator.

Fill behaviour at 750 kcmil: near the limit of building raceway

750 kcmil sits at the practical top of conductors installed in building conduit. Even 4 inch raceway accepts only a small number, so the design is normally one conductor per raceway, tray-mounted, or busway instead of conductors entirely.

The counts here are most useful as a sanity check: if a design requires several 750 kcmil conductors in one raceway, the design almost certainly wants parallel sets of smaller conductors, busway or a switchboard relocation instead.

Source & method: Counts referenced above come from the computed table on this page — how these numbers are derived.

What each raceway type means

  • EMT — EMT (electrical metallic tubing)
  • IMC — IMC (intermediate metal conduit)
  • RMC — RMC (rigid metal conduit)
  • PVC Sch 40 — PVC Schedule 40
  • PVC Sch 80 — PVC Schedule 80

Full fill charts by raceway

Per-type counts for every trade size, plus the cross-type comparison and reverse lookup.

Frequently asked

How many 750 kcmil wires fit in 1/2 inch EMT?
None — this size does not fit 1/2 inch EMT; step up a trade size.
How many 750 kcmil wires fit in 3/4 inch EMT?
0 conductors, using a nominal THHN outside diameter of 1.158 in and the 40% fill rule for three or more conductors.
Do neutrals and grounds count toward fill?
Yes, every conductor in the raceway counts for fill. Grounds are excluded only from the count of current-carrying conductors used for ampacity adjustment.
What is the cross-sectional area of 750 kcmil THHN?
About 1.0532 square inches, from A = π × (OD / 2)² with a nominal insulated OD of 1.158 in.

More on 750 kcmil

Conduit fill for nearby sizes

Same 40% fill rule applied to the sizes either side of this one, wrapping around the range so every size is reachable.