300 kcmil Breaker Size & Ampacity
300 kcmil copper is estimated at 289 A at 75 °C, supporting a 250 A overcurrent device. Breaker pairing and derating shown.
Quick answer
300 kcmil copper pairs with a 250 A breaker at 75 °C terminations, from an estimated ampacity of 289 A. Aluminium of the same size is about 225 A. A continuous load on that circuit should not exceed 231 A, since continuous loads are sized at 125%.
Max breaker (Cu, 75 °C)
250A
Copper 60 / 75 / 90 °C
245 / 289 / 326A
Aluminium 75 °C
225A
Max continuous load
231A
Ampacity and breaker pairing
Estimated ampacity by material and insulation temperature rating, with the largest standard device each supports.
| Material | 60 °C | 75 °C | 90 °C | Max device @ 75 °C |
|---|---|---|---|---|
| Copper | 245 A | 289 A | 326 A | 250 A |
| Aluminium | 191 A | 225 A | 254 A | 225 A |
Formula estimate — source: Ampacity from the site power-law model, not a code table
Derated ampacity and the device that still fits
Ambient temperature and conductor count reduce the usable ampacity before the breaker is chosen.
| Conductors in raceway | 30 °C ambient | 40 °C ambient | 50 °C ambient | 60 °C ambient |
|---|---|---|---|---|
| 3 | 326 A → 250 A | 298 A → 250 A | 266 A → 250 A | 230 A → 225 A |
| 6 | 261 A → 250 A | 238 A → 225 A | 213 A → 200 A | 184 A → 175 A |
| 9 | 228 A → 225 A | 208 A → 200 A | 186 A → 175 A | 161 A → 150 A |
| 15 | 163 A → 150 A | 149 A → 125 A | 133 A → 125 A | 115 A → 110 A |
| 25 | 147 A → 125 A | 134 A → 125 A | 120 A → 110 A | 104 A → 100 A |
Source & method: Continuous-load example: a 231 A continuous load needs 289 A of design current and a 300 A device. Size your own load.
Neighbouring sizes
Frequently asked
- What breaker size for 300 kcmil wire?
- 300 kcmil copper at 75 °C terminations supports up to a 250 A overcurrent device, based on an estimated ampacity of 289 A. Aluminium of the same size supports less: about 225 A.
- How many amps can 300 kcmil handle?
- Estimated 245 A at 60 °C, 289 A at 75 °C and 326 A at 90 °C for copper, at 30 °C ambient with no more than three current-carrying conductors.
- How does a continuous load change the breaker size?
- Continuous loads are sized at 125% of the load current before rounding up to the next standard device rating, so a breaker carries no more than 80% of its rating continuously.
- Can the breaker be larger than the wire ampacity?
- Only in specific permitted cases such as motor and transformer circuits, where the device protects against short circuit and ground fault while overload protection is provided separately. For ordinary branch circuits, the device must not exceed the conductor ampacity after derating.
More on 300 kcmil
Related charts & calculators
- Rigid Conduit Fill ChartRMC and IMC conductor counts per trade size, side by side.
- Sheet Metal Gauge ChartGauge to thickness in inches and millimetres for steel, galvanised and aluminium.
- Rebar Size ChartBar designation, diameter, area and weight per foot.
- Socket Size ChartSAE to metric socket conversion with the closest interchangeable size.
- Pipe Thread ChartNPT nominal size, outside diameter, threads per inch and tap drill.
- Nut Size ChartBolt size to hex nut across-flats wrench size, SAE and metric.