300 kcmil Breaker Size — Amps & Overcurrent Rating

300 kcmil copper is estimated at 289 A at 75 °C, which supports a 250 A overcurrent device. Breaker pairing, continuous-load sizing and derating shown.

Quick answer

300 kcmil copper pairs with a 250 A breaker at 75 °C terminations, from an estimated ampacity of 289 A. Aluminium of the same size is about 225 A. A continuous load on that circuit should not exceed 231 A, since continuous loads are sized at 125%.

Max breaker (Cu, 75 °C)

250A

Copper 60 / 75 / 90 °C

245 / 289 / 326A

Aluminium 75 °C

225A

Max continuous load

231A

Ampacity and breaker pairing

Estimated ampacity by material and insulation temperature rating, with the largest standard device each supports.

Material60 °C75 °C90 °CMax device @ 75 °C
Copper245 A289 A326 A250 A
Aluminium191 A225 A254 A225 A
Formula estimate — source: Ampacity from the site power-law model, not a code table

Derated ampacity and the device that still fits

Ambient temperature and conductor count reduce the usable ampacity before the breaker is chosen.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
3326 A → 250 A298 A → 250 A266 A → 250 A230 A → 225 A
6261 A → 250 A238 A → 225 A213 A → 200 A184 A → 175 A
9228 A → 225 A208 A → 200 A186 A → 175 A161 A → 150 A
15163 A → 150 A149 A → 125 A133 A → 125 A115 A → 110 A
25147 A → 125 A134 A → 125 A120 A → 110 A104 A → 100 A
90 °C insulation, copper, capped in practice by the 75 °C termination rating.

Source & method: Continuous-load example: a 231 A continuous load needs 289 A of design current and a 300 A device. Size your own load.

Neighbouring sizes

Frequently asked

What breaker size for 300 kcmil wire?
300 kcmil copper at 75 °C terminations supports up to a 250 A overcurrent device, based on an estimated ampacity of 289 A. Aluminium of the same size supports less: about 225 A.
How many amps can 300 kcmil handle?
Estimated 245 A at 60 °C, 289 A at 75 °C and 326 A at 90 °C for copper, at 30 °C ambient with no more than three current-carrying conductors.
How does a continuous load change the breaker size?
Continuous loads are sized at 125% of the load current before rounding up to the next standard device rating, so a breaker carries no more than 80% of its rating continuously.
Can the breaker be larger than the wire ampacity?
Only in specific permitted cases such as motor and transformer circuits, where the device protects against short circuit and ground fault while overload protection is provided separately. For ordinary branch circuits, the device must not exceed the conductor ampacity after derating.