18 AWG Breaker Size & Ampacity
18 AWG copper is estimated at 10 A at 75 °C, supporting a — A overcurrent device. Breaker pairing and derating shown.
Quick answer
18 AWG copper pairs with a — A breaker at 75 °C terminations, from an estimated ampacity of 10 A. Aluminium of the same size is about 8 A. A continuous load on that circuit should not exceed 8 A, since continuous loads are sized at 125%.
Max breaker (Cu, 75 °C)
—A
Copper 60 / 75 / 90 °C
8 / 10 / 11A
Aluminium 75 °C
8A
Max continuous load
8A
Ampacity and breaker pairing
Estimated ampacity by material and insulation temperature rating, with the largest standard device each supports.
| Material | 60 °C | 75 °C | 90 °C | Max device @ 75 °C |
|---|---|---|---|---|
| Copper | 8 A | 10 A | 11 A | — |
| Aluminium | 6 A | 8 A | 9 A | — |
Formula estimate — source: Ampacity from the site power-law model, not a code table
Derated ampacity and the device that still fits
Ambient temperature and conductor count reduce the usable ampacity before the breaker is chosen.
| Conductors in raceway | 30 °C ambient | 40 °C ambient | 50 °C ambient | 60 °C ambient |
|---|---|---|---|---|
| 3 | 11 A → — | 10 A → — | 9 A → — | 8 A → — |
| 6 | 9 A → — | 8 A → — | 7 A → — | 6 A → — |
| 9 | 8 A → — | 7 A → — | 6 A → — | 5 A → — |
| 15 | 6 A → — | 5 A → — | 4 A → — | 4 A → — |
| 25 | 5 A → — | 5 A → — | 4 A → — | 3 A → — |
Source & method: Continuous-load example: a 8 A continuous load needs 10 A of design current and a 15 A device. Size your own load.
Neighbouring sizes
Frequently asked
- What breaker size for 18 AWG wire?
- 18 AWG is below the smallest standard branch-circuit device rating and is normally used for control, signal or fixture wiring.
- How many amps can 18 AWG handle?
- Estimated 8 A at 60 °C, 10 A at 75 °C and 11 A at 90 °C for copper, at 30 °C ambient with no more than three current-carrying conductors.
- How does a continuous load change the breaker size?
- Continuous loads are sized at 125% of the load current before rounding up to the next standard device rating, so a breaker carries no more than 80% of its rating continuously.
- Can the breaker be larger than the wire ampacity?
- Only in specific permitted cases such as motor and transformer circuits, where the device protects against short circuit and ground fault while overload protection is provided separately. For ordinary branch circuits, the device must not exceed the conductor ampacity after derating.
More on 18 AWG
Related charts & calculators
- kcmil Wire Size ChartMCM to AWG conversion, circular mils, resistance and ampacity for 250-750 kcmil.
- Conduit Fill ChartMaximum THHN conductors per trade size for every raceway type.
- EMT Conduit Fill ChartConductor counts and internal areas for electrical metallic tubing.
- PVC Conduit Fill ChartSchedule 40 and Schedule 80 conductor counts and usable areas.
- Rigid Conduit Fill ChartRMC and IMC conductor counts per trade size, side by side.
- Sheet Metal Gauge ChartGauge to thickness in inches and millimetres for steel, galvanised and aluminium.