18 AWG Voltage Drop — Max Run Length by Load

Voltage drop for 18 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 11 ft one-way. Full table by load, voltage and distance.

Quick answer

18 AWG copper reaches 3% voltage drop at about 11 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 31.77 V (26.48%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 1,624 circular mils.

3% limit @ 20 A, 120 V

11ft

3% limit @ 20 A, 240 V

22ft

Drop @ 100 ft, 20 A

31.77V

Ω / 1000 ft (Cu)

6.3861

Maximum one-way run length at 3% drop

Copper 18 AWG. Aluminium distances are roughly 62% of these figures.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
5 A45 ft90 ft90 ft209 ft
10 A22 ft45 ft45 ft104 ft
15 A15 ft30 ft30 ft69 ft
20 A11 ft22 ft22 ft52 ft
25 A9 ft18 ft18 ft41 ft
30 A7 ft15 ft15 ft34 ft
40 A5 ft11 ft11 ft26 ft
50 A4 ft9 ft9 ft20 ft
60 A3 ft7 ft7 ft17 ft
80 A2 ft5 ft5 ft13 ft
100 A2 ft4 ft4 ft10 ft

Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.

Voltage drop by distance at common loads

Distance10 A15 A20 A30 A
25 ft3.31%4.96%6.62%9.93%
50 ft6.62%9.93%13.24%19.86%
75 ft9.93%14.89%19.86%29.79%
100 ft13.24%19.86%26.48%39.72%
150 ft19.86%29.79%39.72%59.58%
200 ft26.48%39.72%52.96%79.43%
300 ft39.72%59.58%79.43%119.15%
Percent drop, 120 V single phase, copper.
Published standard — source: Voltage drop from the standard VD formula with trade K constants

Frequently asked

How far can you run 18 AWG wire?
At 20 A on a 120 V single-phase circuit, 18 AWG copper stays under 3% voltage drop for about 11 ft one-way. At 240 V the same load reaches roughly 22 ft, because allowable drop scales with system voltage.
What is the voltage drop of 18 AWG wire per 100 feet?
About 31.77 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
Is 3% voltage drop a code requirement?
It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
Does aluminium change the 18 AWG numbers?
Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.