18 AWG Voltage Drop — Max Run Length by Load
Voltage drop for 18 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 11 ft one-way. Full table by load, voltage and distance.
Quick answer
18 AWG copper reaches 3% voltage drop at about 11 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 31.77 V (26.48%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 1,624 circular mils.
3% limit @ 20 A, 120 V
11ft
3% limit @ 20 A, 240 V
22ft
Drop @ 100 ft, 20 A
31.77V
Ω / 1000 ft (Cu)
6.3861
Maximum one-way run length at 3% drop
Copper 18 AWG. Aluminium distances are roughly 62% of these figures.
| Load | 120 V 1Ø | 240 V 1Ø | 208 V 3Ø | 480 V 3Ø |
|---|---|---|---|---|
| 5 A | 45 ft | 90 ft | 90 ft | 209 ft |
| 10 A | 22 ft | 45 ft | 45 ft | 104 ft |
| 15 A | 15 ft | 30 ft | 30 ft | 69 ft |
| 20 A | 11 ft | 22 ft | 22 ft | 52 ft |
| 25 A | 9 ft | 18 ft | 18 ft | 41 ft |
| 30 A | 7 ft | 15 ft | 15 ft | 34 ft |
| 40 A | 5 ft | 11 ft | 11 ft | 26 ft |
| 50 A | 4 ft | 9 ft | 9 ft | 20 ft |
| 60 A | 3 ft | 7 ft | 7 ft | 17 ft |
| 80 A | 2 ft | 5 ft | 5 ft | 13 ft |
| 100 A | 2 ft | 4 ft | 4 ft | 10 ft |
Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.
Voltage drop by distance at common loads
| Distance | 10 A | 15 A | 20 A | 30 A |
|---|---|---|---|---|
| 25 ft | 3.31% | 4.96% | 6.62% | 9.93% |
| 50 ft | 6.62% | 9.93% | 13.24% | 19.86% |
| 75 ft | 9.93% | 14.89% | 19.86% | 29.79% |
| 100 ft | 13.24% | 19.86% | 26.48% | 39.72% |
| 150 ft | 19.86% | 29.79% | 39.72% | 59.58% |
| 200 ft | 26.48% | 39.72% | 52.96% | 79.43% |
| 300 ft | 39.72% | 59.58% | 79.43% | 119.15% |
Published standard — source: Voltage drop from the standard VD formula with trade K constants
Frequently asked
- How far can you run 18 AWG wire?
- At 20 A on a 120 V single-phase circuit, 18 AWG copper stays under 3% voltage drop for about 11 ft one-way. At 240 V the same load reaches roughly 22 ft, because allowable drop scales with system voltage.
- What is the voltage drop of 18 AWG wire per 100 feet?
- About 31.77 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
- Is 3% voltage drop a code requirement?
- It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
- Does aluminium change the 18 AWG numbers?
- Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.
More on 18 AWG
Related charts & calculators
- Voltage Drop CalculatorPercent drop, end voltage and minimum conductor for any run length.
- Conduit Fill CalculatorFill percentage and maximum conductor count for EMT, RMC, IMC and PVC.
- Breaker Size CalculatorOvercurrent device rating and minimum conductor from load current.
- Wire Ampacity CalculatorDerated ampacity for ambient temperature and bundled conductors.
- Box Fill CalculatorVolume allowances for conductors, clamps, devices and grounds per NEC 314.16.
- Ampacity ChartEstimated allowable ampacity by conductor size, material and insulation rating.