16 AWG Breaker Size — Amps & Overcurrent Rating

16 AWG copper is estimated at 13 A at 75 °C, which supports a — A overcurrent device. Breaker pairing, continuous-load sizing and derating shown.

Quick answer

16 AWG copper pairs with a A breaker at 75 °C terminations, from an estimated ampacity of 13 A. Aluminium of the same size is about 10 A. A continuous load on that circuit should not exceed 10 A, since continuous loads are sized at 125%.

Max breaker (Cu, 75 °C)

A

Copper 60 / 75 / 90 °C

11 / 13 / 15A

Aluminium 75 °C

10A

Max continuous load

10A

Ampacity and breaker pairing

Estimated ampacity by material and insulation temperature rating, with the largest standard device each supports.

Material60 °C75 °C90 °CMax device @ 75 °C
Copper11 A13 A15 A
Aluminium9 A10 A12 A
Formula estimate — source: Ampacity from the site power-law model, not a code table

Derated ampacity and the device that still fits

Ambient temperature and conductor count reduce the usable ampacity before the breaker is chosen.

Conductors in raceway30 °C ambient40 °C ambient50 °C ambient60 °C ambient
315 A → —14 A → —12 A → —11 A → —
612 A → —11 A → —10 A → —8 A → —
911 A → —10 A → —9 A → —7 A → —
158 A → —7 A → —6 A → —5 A → —
257 A → —6 A → —6 A → —5 A → —
90 °C insulation, copper, capped in practice by the 75 °C termination rating.

Source & method: Continuous-load example: a 10 A continuous load needs 13 A of design current and a 15 A device. Size your own load.

Neighbouring sizes

Frequently asked

What breaker size for 16 AWG wire?
16 AWG is below the smallest standard branch-circuit device rating and is normally used for control, signal or fixture wiring.
How many amps can 16 AWG handle?
Estimated 11 A at 60 °C, 13 A at 75 °C and 15 A at 90 °C for copper, at 30 °C ambient with no more than three current-carrying conductors.
How does a continuous load change the breaker size?
Continuous loads are sized at 125% of the load current before rounding up to the next standard device rating, so a breaker carries no more than 80% of its rating continuously.
Can the breaker be larger than the wire ampacity?
Only in specific permitted cases such as motor and transformer circuits, where the device protects against short circuit and ground fault while overload protection is provided separately. For ordinary branch circuits, the device must not exceed the conductor ampacity after derating.