16 AWG Voltage Drop — Max Run Length by Load

Voltage drop for 16 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 18 ft one-way. Full table by load, voltage and distance.

Quick answer

16 AWG copper reaches 3% voltage drop at about 18 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 19.98 V (16.65%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 2,583 circular mils.

3% limit @ 20 A, 120 V

18ft

3% limit @ 20 A, 240 V

36ft

Drop @ 100 ft, 20 A

19.98V

Ω / 1000 ft (Cu)

4.0151

Maximum one-way run length at 3% drop

Copper 16 AWG. Aluminium distances are roughly 62% of these figures.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
5 A72 ft144 ft144 ft332 ft
10 A36 ft72 ft72 ft166 ft
15 A24 ft48 ft48 ft110 ft
20 A18 ft36 ft36 ft83 ft
25 A14 ft28 ft28 ft66 ft
30 A12 ft24 ft24 ft55 ft
40 A9 ft18 ft18 ft41 ft
50 A7 ft14 ft14 ft33 ft
60 A6 ft12 ft12 ft27 ft
80 A4 ft9 ft9 ft20 ft
100 A3 ft7 ft7 ft16 ft

Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.

Voltage drop by distance at common loads

Distance10 A15 A20 A30 A
25 ft2.08%3.12%4.16%6.24%
50 ft4.16%6.24%8.32%12.49%
75 ft6.24%9.36%12.49%18.73%
100 ft8.32%12.49%16.65%24.97%
150 ft12.49%18.73%24.97%37.46%
200 ft16.65%24.97%33.29%49.94%
300 ft24.97%37.46%49.94%74.91%
Percent drop, 120 V single phase, copper.
Published standard — source: Voltage drop from the standard VD formula with trade K constants

Frequently asked

How far can you run 16 AWG wire?
At 20 A on a 120 V single-phase circuit, 16 AWG copper stays under 3% voltage drop for about 18 ft one-way. At 240 V the same load reaches roughly 36 ft, because allowable drop scales with system voltage.
What is the voltage drop of 16 AWG wire per 100 feet?
About 19.98 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
Is 3% voltage drop a code requirement?
It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
Does aluminium change the 16 AWG numbers?
Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.