16 AWG Voltage Drop — Max Run Length by Load
Voltage drop for 16 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 18 ft one-way. Full table by load, voltage and distance.
Quick answer
16 AWG copper reaches 3% voltage drop at about 18 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 19.98 V (16.65%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 2,583 circular mils.
3% limit @ 20 A, 120 V
18ft
3% limit @ 20 A, 240 V
36ft
Drop @ 100 ft, 20 A
19.98V
Ω / 1000 ft (Cu)
4.0151
Maximum one-way run length at 3% drop
Copper 16 AWG. Aluminium distances are roughly 62% of these figures.
| Load | 120 V 1Ø | 240 V 1Ø | 208 V 3Ø | 480 V 3Ø |
|---|---|---|---|---|
| 5 A | 72 ft | 144 ft | 144 ft | 332 ft |
| 10 A | 36 ft | 72 ft | 72 ft | 166 ft |
| 15 A | 24 ft | 48 ft | 48 ft | 110 ft |
| 20 A | 18 ft | 36 ft | 36 ft | 83 ft |
| 25 A | 14 ft | 28 ft | 28 ft | 66 ft |
| 30 A | 12 ft | 24 ft | 24 ft | 55 ft |
| 40 A | 9 ft | 18 ft | 18 ft | 41 ft |
| 50 A | 7 ft | 14 ft | 14 ft | 33 ft |
| 60 A | 6 ft | 12 ft | 12 ft | 27 ft |
| 80 A | 4 ft | 9 ft | 9 ft | 20 ft |
| 100 A | 3 ft | 7 ft | 7 ft | 16 ft |
Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.
Voltage drop by distance at common loads
| Distance | 10 A | 15 A | 20 A | 30 A |
|---|---|---|---|---|
| 25 ft | 2.08% | 3.12% | 4.16% | 6.24% |
| 50 ft | 4.16% | 6.24% | 8.32% | 12.49% |
| 75 ft | 6.24% | 9.36% | 12.49% | 18.73% |
| 100 ft | 8.32% | 12.49% | 16.65% | 24.97% |
| 150 ft | 12.49% | 18.73% | 24.97% | 37.46% |
| 200 ft | 16.65% | 24.97% | 33.29% | 49.94% |
| 300 ft | 24.97% | 37.46% | 49.94% | 74.91% |
Published standard — source: Voltage drop from the standard VD formula with trade K constants
Frequently asked
- How far can you run 16 AWG wire?
- At 20 A on a 120 V single-phase circuit, 16 AWG copper stays under 3% voltage drop for about 18 ft one-way. At 240 V the same load reaches roughly 36 ft, because allowable drop scales with system voltage.
- What is the voltage drop of 16 AWG wire per 100 feet?
- About 19.98 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
- Is 3% voltage drop a code requirement?
- It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
- Does aluminium change the 16 AWG numbers?
- Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.
More on 16 AWG
Related charts & calculators
- Voltage Drop CalculatorPercent drop, end voltage and minimum conductor for any run length.
- Conduit Fill CalculatorFill percentage and maximum conductor count for EMT, RMC, IMC and PVC.
- Breaker Size CalculatorOvercurrent device rating and minimum conductor from load current.
- Wire Ampacity CalculatorDerated ampacity for ambient temperature and bundled conductors.
- Box Fill CalculatorVolume allowances for conductors, clamps, devices and grounds per NEC 314.16.
- Ampacity ChartEstimated allowable ampacity by conductor size, material and insulation rating.