8 AWG Voltage Drop — Max Run Length by Load
Voltage drop for 8 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 115 ft one-way. Full table by load, voltage and distance.
Quick answer
8 AWG copper reaches 3% voltage drop at about 115 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 3.13 V (2.6%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 16,510 circular mils.
3% limit @ 20 A, 120 V
115ft
3% limit @ 20 A, 240 V
230ft
Drop @ 100 ft, 20 A
3.13V
Ω / 1000 ft (Cu)
0.6282
Maximum one-way run length at 3% drop
Copper 8 AWG. Aluminium distances are roughly 62% of these figures.
| Load | 120 V 1Ø | 240 V 1Ø | 208 V 3Ø | 480 V 3Ø |
|---|---|---|---|---|
| 5 A | 460 ft | 921 ft | 922 ft | 2,128 ft |
| 10 A | 230 ft | 460 ft | 461 ft | 1,064 ft |
| 15 A | 153 ft | 307 ft | 307 ft | 709 ft |
| 20 A | 115 ft | 230 ft | 230 ft | 532 ft |
| 25 A | 92 ft | 184 ft | 184 ft | 425 ft |
| 30 A | 76 ft | 153 ft | 153 ft | 354 ft |
| 40 A | 57 ft | 115 ft | 115 ft | 266 ft |
| 50 A | 46 ft | 92 ft | 92 ft | 212 ft |
| 60 A | 38 ft | 76 ft | 76 ft | 177 ft |
| 80 A | 28 ft | 57 ft | 57 ft | 133 ft |
| 100 A | 23 ft | 46 ft | 46 ft | 106 ft |
Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.
Voltage drop by distance at common loads
| Distance | 10 A | 15 A | 20 A | 30 A |
|---|---|---|---|---|
| 25 ft | 0.33% | 0.49% | 0.65% | 0.98% |
| 50 ft | 0.65% | 0.98% | 1.3% | 1.95% |
| 75 ft | 0.98% | 1.47% | 1.95% | 2.93% |
| 100 ft | 1.3% | 1.95% | 2.6% | 3.91% |
| 150 ft | 1.95% | 2.93% | 3.91% | 5.86% |
| 200 ft | 2.6% | 3.91% | 5.21% | 7.81% |
| 300 ft | 3.91% | 5.86% | 7.81% | 11.72% |
Published standard — source: Voltage drop from the standard VD formula with trade K constants
Frequently asked
- How far can you run 8 AWG wire?
- At 20 A on a 120 V single-phase circuit, 8 AWG copper stays under 3% voltage drop for about 115 ft one-way. At 240 V the same load reaches roughly 230 ft, because allowable drop scales with system voltage.
- What is the voltage drop of 8 AWG wire per 100 feet?
- About 3.13 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
- Is 3% voltage drop a code requirement?
- It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
- Does aluminium change the 8 AWG numbers?
- Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.
More on 8 AWG
Related charts & calculators
- Voltage Drop CalculatorPercent drop, end voltage and minimum conductor for any run length.
- Conduit Fill CalculatorFill percentage and maximum conductor count for EMT, RMC, IMC and PVC.
- Breaker Size CalculatorOvercurrent device rating and minimum conductor from load current.
- Wire Ampacity CalculatorDerated ampacity for ambient temperature and bundled conductors.
- Box Fill CalculatorVolume allowances for conductors, clamps, devices and grounds per NEC 314.16.
- Ampacity ChartEstimated allowable ampacity by conductor size, material and insulation rating.