400 kcmil Voltage Drop — Max Run Length by Load

Voltage drop for 400 kcmil copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 2790 ft one-way. Full table by load, voltage and distance.

Quick answer

400 kcmil copper reaches 3% voltage drop at about 2790 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 0.13 V (0.11%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 400,000 circular mils.

3% limit @ 20 A, 120 V

2790ft

3% limit @ 20 A, 240 V

5581ft

Drop @ 100 ft, 20 A

0.13V

Ω / 1000 ft (Cu)

0.0259

Maximum one-way run length at 3% drop

Copper 400 kcmil. Aluminium distances are roughly 62% of these figures.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
5 A11,162 ft22,325 ft22,342 ft51,560 ft
10 A5,581 ft11,162 ft11,171 ft25,780 ft
15 A3,720 ft7,441 ft7,447 ft17,186 ft
20 A2,790 ft5,581 ft5,585 ft12,890 ft
25 A2,232 ft4,465 ft4,468 ft10,312 ft
30 A1,860 ft3,720 ft3,723 ft8,593 ft
40 A1,395 ft2,790 ft2,792 ft6,445 ft
50 A1,116 ft2,232 ft2,234 ft5,156 ft
60 A930 ft1,860 ft1,861 ft4,296 ft
80 A697 ft1,395 ft1,396 ft3,222 ft
100 A558 ft1,116 ft1,117 ft2,578 ft

Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.

Voltage drop by distance at common loads

Distance10 A15 A20 A30 A
25 ft0.01%0.02%0.03%0.04%
50 ft0.03%0.04%0.05%0.08%
75 ft0.04%0.06%0.08%0.12%
100 ft0.05%0.08%0.11%0.16%
150 ft0.08%0.12%0.16%0.24%
200 ft0.11%0.16%0.22%0.32%
300 ft0.16%0.24%0.32%0.48%
Percent drop, 120 V single phase, copper.
Published standard — source: Voltage drop from the standard VD formula with trade K constants

Frequently asked

How far can you run 400 kcmil wire?
At 20 A on a 120 V single-phase circuit, 400 kcmil copper stays under 3% voltage drop for about 2790 ft one-way. At 240 V the same load reaches roughly 5581 ft, because allowable drop scales with system voltage.
What is the voltage drop of 400 kcmil wire per 100 feet?
About 0.13 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
Is 3% voltage drop a code requirement?
It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
Does aluminium change the 400 kcmil numbers?
Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.