4 AWG Voltage Drop — Max Run Length by Load

Voltage drop for 4 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 291 ft one-way. Full table by load, voltage and distance.

Quick answer

4 AWG copper reaches 3% voltage drop at about 291 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 1.24 V (1.03%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 41,741 circular mils.

3% limit @ 20 A, 120 V

291ft

3% limit @ 20 A, 240 V

582ft

Drop @ 100 ft, 20 A

1.24V

Ω / 1000 ft (Cu)

0.2485

Maximum one-way run length at 3% drop

Copper 4 AWG. Aluminium distances are roughly 62% of these figures.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
5 A1,164 ft2,329 ft2,331 ft5,380 ft
10 A582 ft1,164 ft1,165 ft2,690 ft
15 A388 ft776 ft777 ft1,793 ft
20 A291 ft582 ft582 ft1,345 ft
25 A232 ft465 ft466 ft1,076 ft
30 A194 ft388 ft388 ft896 ft
40 A145 ft291 ft291 ft672 ft
50 A116 ft232 ft233 ft538 ft
60 A97 ft194 ft194 ft448 ft
80 A72 ft145 ft145 ft336 ft
100 A58 ft116 ft116 ft269 ft

Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.

Voltage drop by distance at common loads

Distance10 A15 A20 A30 A
25 ft0.13%0.19%0.26%0.39%
50 ft0.26%0.39%0.52%0.77%
75 ft0.39%0.58%0.77%1.16%
100 ft0.52%0.77%1.03%1.55%
150 ft0.77%1.16%1.55%2.32%
200 ft1.03%1.55%2.06%3.09%
300 ft1.55%2.32%3.09%4.64%
Percent drop, 120 V single phase, copper.
Published standard — source: Voltage drop from the standard VD formula with trade K constants

Frequently asked

How far can you run 4 AWG wire?
At 20 A on a 120 V single-phase circuit, 4 AWG copper stays under 3% voltage drop for about 291 ft one-way. At 240 V the same load reaches roughly 582 ft, because allowable drop scales with system voltage.
What is the voltage drop of 4 AWG wire per 100 feet?
About 1.24 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
Is 3% voltage drop a code requirement?
It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
Does aluminium change the 4 AWG numbers?
Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.