3 AWG Voltage Drop — Max Run Length by Load

Voltage drop for 3 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 367 ft one-way. Full table by load, voltage and distance.

Quick answer

3 AWG copper reaches 3% voltage drop at about 367 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 0.98 V (0.82%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 52,635 circular mils.

3% limit @ 20 A, 120 V

367ft

3% limit @ 20 A, 240 V

734ft

Drop @ 100 ft, 20 A

0.98V

Ω / 1000 ft (Cu)

0.1970

Maximum one-way run length at 3% drop

Copper 3 AWG. Aluminium distances are roughly 62% of these figures.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
5 A1,468 ft2,937 ft2,940 ft6,784 ft
10 A734 ft1,468 ft1,470 ft3,392 ft
15 A489 ft979 ft980 ft2,261 ft
20 A367 ft734 ft735 ft1,696 ft
25 A293 ft587 ft588 ft1,356 ft
30 A244 ft489 ft490 ft1,130 ft
40 A183 ft367 ft367 ft848 ft
50 A146 ft293 ft294 ft678 ft
60 A122 ft244 ft245 ft565 ft
80 A91 ft183 ft183 ft424 ft
100 A73 ft146 ft147 ft339 ft

Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.

Voltage drop by distance at common loads

Distance10 A15 A20 A30 A
25 ft0.1%0.15%0.2%0.31%
50 ft0.2%0.31%0.41%0.61%
75 ft0.31%0.46%0.61%0.92%
100 ft0.41%0.61%0.82%1.23%
150 ft0.61%0.92%1.23%1.84%
200 ft0.82%1.23%1.63%2.45%
300 ft1.23%1.84%2.45%3.68%
Percent drop, 120 V single phase, copper.
Published standard — source: Voltage drop from the standard VD formula with trade K constants

Frequently asked

How far can you run 3 AWG wire?
At 20 A on a 120 V single-phase circuit, 3 AWG copper stays under 3% voltage drop for about 367 ft one-way. At 240 V the same load reaches roughly 734 ft, because allowable drop scales with system voltage.
What is the voltage drop of 3 AWG wire per 100 feet?
About 0.98 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
Is 3% voltage drop a code requirement?
It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
Does aluminium change the 3 AWG numbers?
Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.