3 AWG Voltage Drop — Max Run Length by Load
Voltage drop for 3 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 367 ft one-way. Full table by load, voltage and distance.
Quick answer
3 AWG copper reaches 3% voltage drop at about 367 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 0.98 V (0.82%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 52,635 circular mils.
3% limit @ 20 A, 120 V
367ft
3% limit @ 20 A, 240 V
734ft
Drop @ 100 ft, 20 A
0.98V
Ω / 1000 ft (Cu)
0.1970
Maximum one-way run length at 3% drop
Copper 3 AWG. Aluminium distances are roughly 62% of these figures.
| Load | 120 V 1Ø | 240 V 1Ø | 208 V 3Ø | 480 V 3Ø |
|---|---|---|---|---|
| 5 A | 1,468 ft | 2,937 ft | 2,940 ft | 6,784 ft |
| 10 A | 734 ft | 1,468 ft | 1,470 ft | 3,392 ft |
| 15 A | 489 ft | 979 ft | 980 ft | 2,261 ft |
| 20 A | 367 ft | 734 ft | 735 ft | 1,696 ft |
| 25 A | 293 ft | 587 ft | 588 ft | 1,356 ft |
| 30 A | 244 ft | 489 ft | 490 ft | 1,130 ft |
| 40 A | 183 ft | 367 ft | 367 ft | 848 ft |
| 50 A | 146 ft | 293 ft | 294 ft | 678 ft |
| 60 A | 122 ft | 244 ft | 245 ft | 565 ft |
| 80 A | 91 ft | 183 ft | 183 ft | 424 ft |
| 100 A | 73 ft | 146 ft | 147 ft | 339 ft |
Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.
Voltage drop by distance at common loads
| Distance | 10 A | 15 A | 20 A | 30 A |
|---|---|---|---|---|
| 25 ft | 0.1% | 0.15% | 0.2% | 0.31% |
| 50 ft | 0.2% | 0.31% | 0.41% | 0.61% |
| 75 ft | 0.31% | 0.46% | 0.61% | 0.92% |
| 100 ft | 0.41% | 0.61% | 0.82% | 1.23% |
| 150 ft | 0.61% | 0.92% | 1.23% | 1.84% |
| 200 ft | 0.82% | 1.23% | 1.63% | 2.45% |
| 300 ft | 1.23% | 1.84% | 2.45% | 3.68% |
Published standard — source: Voltage drop from the standard VD formula with trade K constants
Frequently asked
- How far can you run 3 AWG wire?
- At 20 A on a 120 V single-phase circuit, 3 AWG copper stays under 3% voltage drop for about 367 ft one-way. At 240 V the same load reaches roughly 734 ft, because allowable drop scales with system voltage.
- What is the voltage drop of 3 AWG wire per 100 feet?
- About 0.98 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
- Is 3% voltage drop a code requirement?
- It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
- Does aluminium change the 3 AWG numbers?
- Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.
More on 3 AWG
Related charts & calculators
- Voltage Drop CalculatorPercent drop, end voltage and minimum conductor for any run length.
- Conduit Fill CalculatorFill percentage and maximum conductor count for EMT, RMC, IMC and PVC.
- Breaker Size CalculatorOvercurrent device rating and minimum conductor from load current.
- Wire Ampacity CalculatorDerated ampacity for ambient temperature and bundled conductors.
- Box Fill CalculatorVolume allowances for conductors, clamps, devices and grounds per NEC 314.16.
- Ampacity ChartEstimated allowable ampacity by conductor size, material and insulation rating.