14 AWG Voltage Drop — Max Run Length by Load

Voltage drop for 14 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 28 ft one-way. Full table by load, voltage and distance.

Quick answer

14 AWG copper reaches 3% voltage drop at about 28 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 12.56 V (10.47%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 4,107 circular mils.

3% limit @ 20 A, 120 V

28ft

3% limit @ 20 A, 240 V

57ft

Drop @ 100 ft, 20 A

12.56V

Ω / 1000 ft (Cu)

2.5252

Maximum one-way run length at 3% drop

Copper 14 AWG. Aluminium distances are roughly 62% of these figures.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
5 A114 ft229 ft229 ft529 ft
10 A57 ft114 ft114 ft264 ft
15 A38 ft76 ft76 ft176 ft
20 A28 ft57 ft57 ft132 ft
25 A22 ft45 ft45 ft105 ft
30 A19 ft38 ft38 ft88 ft
40 A14 ft28 ft28 ft66 ft
50 A11 ft22 ft22 ft52 ft
60 A9 ft19 ft19 ft44 ft
80 A7 ft14 ft14 ft33 ft
100 A5 ft11 ft11 ft26 ft

Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.

Voltage drop by distance at common loads

Distance10 A15 A20 A30 A
25 ft1.31%1.96%2.62%3.93%
50 ft2.62%3.93%5.23%7.85%
75 ft3.93%5.89%7.85%11.78%
100 ft5.23%7.85%10.47%15.7%
150 ft7.85%11.78%15.7%23.56%
200 ft10.47%15.7%20.94%31.41%
300 ft15.7%23.56%31.41%47.11%
Percent drop, 120 V single phase, copper.
Published standard — source: Voltage drop from the standard VD formula with trade K constants

Frequently asked

How far can you run 14 AWG wire?
At 20 A on a 120 V single-phase circuit, 14 AWG copper stays under 3% voltage drop for about 28 ft one-way. At 240 V the same load reaches roughly 57 ft, because allowable drop scales with system voltage.
What is the voltage drop of 14 AWG wire per 100 feet?
About 12.56 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
Is 3% voltage drop a code requirement?
It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
Does aluminium change the 14 AWG numbers?
Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.