12 AWG Voltage Drop — Max Run Length by Load

Voltage drop for 12 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 45 ft one-way. Full table by load, voltage and distance.

Quick answer

12 AWG copper reaches 3% voltage drop at about 45 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 7.9 V (6.58%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 6,530 circular mils.

3% limit @ 20 A, 120 V

45ft

3% limit @ 20 A, 240 V

91ft

Drop @ 100 ft, 20 A

7.9V

Ω / 1000 ft (Cu)

1.5882

Maximum one-way run length at 3% drop

Copper 12 AWG. Aluminium distances are roughly 62% of these figures.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
5 A182 ft364 ft364 ft841 ft
10 A91 ft182 ft182 ft420 ft
15 A60 ft121 ft121 ft280 ft
20 A45 ft91 ft91 ft210 ft
25 A36 ft72 ft72 ft168 ft
30 A30 ft60 ft60 ft140 ft
40 A22 ft45 ft45 ft105 ft
50 A18 ft36 ft36 ft84 ft
60 A15 ft30 ft30 ft70 ft
80 A11 ft22 ft22 ft52 ft
100 A9 ft18 ft18 ft42 ft

Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.

Voltage drop by distance at common loads

Distance10 A15 A20 A30 A
25 ft0.82%1.23%1.65%2.47%
50 ft1.65%2.47%3.29%4.94%
75 ft2.47%3.7%4.94%7.41%
100 ft3.29%4.94%6.58%9.88%
150 ft4.94%7.41%9.88%14.82%
200 ft6.58%9.88%13.17%19.75%
300 ft9.88%14.82%19.75%29.63%
Percent drop, 120 V single phase, copper.
Published standard — source: Voltage drop from the standard VD formula with trade K constants

Frequently asked

How far can you run 12 AWG wire?
At 20 A on a 120 V single-phase circuit, 12 AWG copper stays under 3% voltage drop for about 45 ft one-way. At 240 V the same load reaches roughly 91 ft, because allowable drop scales with system voltage.
What is the voltage drop of 12 AWG wire per 100 feet?
About 7.9 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
Is 3% voltage drop a code requirement?
It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
Does aluminium change the 12 AWG numbers?
Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.