1 AWG Voltage Drop — Max Run Length by Load

Voltage drop for 1 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 583 ft one-way. Full table by load, voltage and distance.

Quick answer

1 AWG copper reaches 3% voltage drop at about 583 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 0.62 V (0.51%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 83,693 circular mils.

3% limit @ 20 A, 120 V

583ft

3% limit @ 20 A, 240 V

1167ft

Drop @ 100 ft, 20 A

0.62V

Ω / 1000 ft (Cu)

0.1239

Maximum one-way run length at 3% drop

Copper 1 AWG. Aluminium distances are roughly 62% of these figures.

Load120 V 1Ø240 V 1Ø208 V 3Ø480 V 3Ø
5 A2,335 ft4,671 ft4,674 ft10,788 ft
10 A1,167 ft2,335 ft2,337 ft5,394 ft
15 A778 ft1,557 ft1,558 ft3,596 ft
20 A583 ft1,167 ft1,168 ft2,697 ft
25 A467 ft934 ft934 ft2,157 ft
30 A389 ft778 ft779 ft1,798 ft
40 A291 ft583 ft584 ft1,348 ft
50 A233 ft467 ft467 ft1,078 ft
60 A194 ft389 ft389 ft899 ft
80 A145 ft291 ft292 ft674 ft
100 A116 ft233 ft233 ft539 ft

Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.

Voltage drop by distance at common loads

Distance10 A15 A20 A30 A
25 ft0.06%0.1%0.13%0.19%
50 ft0.13%0.19%0.26%0.39%
75 ft0.19%0.29%0.39%0.58%
100 ft0.26%0.39%0.51%0.77%
150 ft0.39%0.58%0.77%1.16%
200 ft0.51%0.77%1.03%1.54%
300 ft0.77%1.16%1.54%2.31%
Percent drop, 120 V single phase, copper.
Published standard — source: Voltage drop from the standard VD formula with trade K constants

Frequently asked

How far can you run 1 AWG wire?
At 20 A on a 120 V single-phase circuit, 1 AWG copper stays under 3% voltage drop for about 583 ft one-way. At 240 V the same load reaches roughly 1167 ft, because allowable drop scales with system voltage.
What is the voltage drop of 1 AWG wire per 100 feet?
About 0.62 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
Is 3% voltage drop a code requirement?
It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
Does aluminium change the 1 AWG numbers?
Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.