1 AWG Voltage Drop — Max Run Length by Load
Voltage drop for 1 AWG copper and aluminium: at 20 A on 120 V single phase the 3% limit is reached at about 583 ft one-way. Full table by load, voltage and distance.
Quick answer
1 AWG copper reaches 3% voltage drop at about 583 ft one-way carrying 20 A on a 120 V single-phase circuit. At 100 ft the same load drops 0.62 V (0.51%), calculated as VD = 2 × K × I × L / cmil with K = 12.9 for copper and 83,693 circular mils.
3% limit @ 20 A, 120 V
583ft
3% limit @ 20 A, 240 V
1167ft
Drop @ 100 ft, 20 A
0.62V
Ω / 1000 ft (Cu)
0.1239
Maximum one-way run length at 3% drop
Copper 1 AWG. Aluminium distances are roughly 62% of these figures.
| Load | 120 V 1Ø | 240 V 1Ø | 208 V 3Ø | 480 V 3Ø |
|---|---|---|---|---|
| 5 A | 2,335 ft | 4,671 ft | 4,674 ft | 10,788 ft |
| 10 A | 1,167 ft | 2,335 ft | 2,337 ft | 5,394 ft |
| 15 A | 778 ft | 1,557 ft | 1,558 ft | 3,596 ft |
| 20 A | 583 ft | 1,167 ft | 1,168 ft | 2,697 ft |
| 25 A | 467 ft | 934 ft | 934 ft | 2,157 ft |
| 30 A | 389 ft | 778 ft | 779 ft | 1,798 ft |
| 40 A | 291 ft | 583 ft | 584 ft | 1,348 ft |
| 50 A | 233 ft | 467 ft | 467 ft | 1,078 ft |
| 60 A | 194 ft | 389 ft | 389 ft | 899 ft |
| 80 A | 145 ft | 291 ft | 292 ft | 674 ft |
| 100 A | 116 ft | 233 ft | 233 ft | 539 ft |
Source & method: Derived from VD = 2 × K × I × L / cmil (1.732 × K × I × L / cmil for three phase), solved for L at 3% of nominal voltage. Run your exact circuit.
Voltage drop by distance at common loads
| Distance | 10 A | 15 A | 20 A | 30 A |
|---|---|---|---|---|
| 25 ft | 0.06% | 0.1% | 0.13% | 0.19% |
| 50 ft | 0.13% | 0.19% | 0.26% | 0.39% |
| 75 ft | 0.19% | 0.29% | 0.39% | 0.58% |
| 100 ft | 0.26% | 0.39% | 0.51% | 0.77% |
| 150 ft | 0.39% | 0.58% | 0.77% | 1.16% |
| 200 ft | 0.51% | 0.77% | 1.03% | 1.54% |
| 300 ft | 0.77% | 1.16% | 1.54% | 2.31% |
Published standard — source: Voltage drop from the standard VD formula with trade K constants
Frequently asked
- How far can you run 1 AWG wire?
- At 20 A on a 120 V single-phase circuit, 1 AWG copper stays under 3% voltage drop for about 583 ft one-way. At 240 V the same load reaches roughly 1167 ft, because allowable drop scales with system voltage.
- What is the voltage drop of 1 AWG wire per 100 feet?
- About 0.62 V at 20 A on 120 V single phase, using VD = 2 × K × I × L / cmil with K = 12.9 for copper.
- Is 3% voltage drop a code requirement?
- It is a recommendation, not a mandatory limit, in most adopted codes: roughly 3% on the branch circuit and 5% total including the feeder. Some local amendments and specifications do make it enforceable, so check what applies to your job.
- Does aluminium change the 1 AWG numbers?
- Yes. Aluminium uses K = 21.2 instead of 12.9, so drop is about 64% higher for the same size and run, and allowable distance falls by roughly the same proportion.
More on 1 AWG
Related charts & calculators
- Voltage Drop CalculatorPercent drop, end voltage and minimum conductor for any run length.
- Conduit Fill CalculatorFill percentage and maximum conductor count for EMT, RMC, IMC and PVC.
- Breaker Size CalculatorOvercurrent device rating and minimum conductor from load current.
- Wire Ampacity CalculatorDerated ampacity for ambient temperature and bundled conductors.
- Box Fill CalculatorVolume allowances for conductors, clamps, devices and grounds per NEC 314.16.
- Ampacity ChartEstimated allowable ampacity by conductor size, material and insulation rating.